Three Phase Amps
Purpose
Electrical services are
usually sized by amperage, kilovolt-amps (kVA), or by horsepower (HP)
requirements. In order to size metering equipment properly, it is often
necessary to calculate amps when the transformer size (kVA) is known. Never get
in a habit of adding amps! However, when calculating amps based upon installed
kVA capacity, you do need to add up the total kVA. The correct formula is given
below for calculating three phase amps. This formula works for transformer
banks with closed Wye or Delta secondary (3 transformers) configurations. The
key to using this formula is to use the line to line voltage provided by the
transformer bank, not the line to neutral voltage!
The
following formula may be used for calculating three-phase amps:
kVA X
1,000
Three-phase amps = -----------------------------------------
1.732 X Line to Line voltage
Example 1:
Assume you are using 3 – 100 kVA 120/240 volt transformers. The line to line
voltage of the transformer bank is 240 volts. Therefore, use 240 volts in the
formula. Since you are using 3 – 100 kVA transformers, the total capacity will
be 300 kVA.
300 kVA X 1,000 300,000 VA
Three-phase amps = ------------------------- = --------------------- =
721.71 amps
1.732 X 240 V
415.68V
Rule of Thumb
To avoid
using the above formula, use the following chart for an Amps per kVA constant:
Line to
Line Amps
Voltage
per kVA
208
volts = 2.8
240
volts = 2.4
480 volts = 1.2
Example 2:
Assume you are using 3 – 100 kVA 120/240 volt transformers. The line to line
voltage of the transformer bank is 240 volts. Therefore, use 2.4 for the Amps
per kVA constant in the formula. Since you are using
3 – 100 kVA transformers the total capacity will be 300 kVA.
Amps per
Three-phase amps = kVA Constant X Total kVA = 2.4 X 300 kVA = 720
amps
Notice the answer is
extremely close to the answer given by the exact formula used in example 1.
Sizing equipment is made very easy by remembering these three little Amps per
kVA constants. Simply choose the correct line to line voltage, multiply the
corresponding Amps per kVA constant times the total installed transformer
capacity and you are done. No long formula, no division, no square root of 3,
etc…
Example 3:
Assume you are using 3 – 25 kVA 120/240 volt transformers with paralleled
windings for a 120/208 volt Wye secondary. The line to line voltage of the
transformer bank is 208 volts. Therefore, use 2.8 for the Amps per kVA constant
in the formula. Since you are using 3 – 25 kVA transformers the total capacity
will be 75 kVA.
Amps per
Three-phase amps = kVA Constant X Total kVA = 2.8 X 75 kVA = 210 amps
Once again, sizing equipment is made very easy by using the appropriate Amps
per kVA constant.
Example 4:
Assume you are using
3 – 37.5 kVA 240/480 volt transformers with a 480 volt secondary. The line to
line voltage of the transformer bank is 480 volts. Therefore, use 1.2 for the
Amps per kVA constant in the formula. Since you are using 3 – 37.5 kVA
transformers the total capacity will be 112.5 kVA.
Amps per
Three-phase amps = kVA Constant X Total kVA = 1.2 X 112.5 kVA = 135
amps
Open Delta Transformer Secondary
An open Delta transformer
secondary only requires two transformers. However, the total transformer
capacity is reduced to 86% of the total kVA. Therefore, the previously used
rule of thumb may be applied along with 86% to calculate three phase amps for
open Delta transformer banks.
Example 5:
Assume you are using 2 – 50 kVA 120/240 volt transformers with a 240 volt open
Delta secondary. The line to line voltage of the transformer bank is 240
volts. Therefore, use 2.4 for the Amps per kVA constant in the formula. Since
you are using 2 – 50 kVA transformers the total capacity will be 100 kVA X
86% = 86 kVA.
Amps per
Three-phase amps = kVA Constant X Total kVA = 2.4 X 86 kVA = 206.4
amps
Never Add Amps!
Adding amps may be done under
certain circumstances, however, it is also responsible for many incorrectly
sized electrical installations. Therefore, unless you are certain you
thoroughly understand how circuits work, it is best not to get in the habit of
adding amps.
Example 6:
In the following diagram, amperage has been measured on all three phases. Each
phase has been measured at 100 amps. This is a balanced 100 amp three phase
load. Not a 300 amp load! The conductors connecting the transformers and the
rest of the main secondary service must be capable of carrying 100 amps not 300
amps. Once again, do not get in the habit of adding amps!
Metering Equipment & Transformer Sizing
Example 7:
An electrician says a new three-phase 120/240 volt Delta service will require up
to 600 amps. Use the previously stated rule of thumb in reverse. Divide 600
amps by the Amps per kVA constant for a line to line voltage of 240 volts. 600
divided by 2.4 is 250. 250 is the total kVA required. Each transformer will
need to be a minimum of 83 kVA to carry a balanced 600 amp load. Many
electrical utilities would install 3 – 75 kVA transformers even though they are
only capable of delivering 540 amps on a continuous basis. If 600 amps are only
required for short periods of time, and the transformers are fused properly, the
transformers will not be harmed. If in doubt, install 3 – 100 kVA transformers,
which can provide 720 amps. Current transformers with a 200/5 ratio with a RF
of 3.0 would be appropriate. Be sure to use a class 20 meter since the 200/5
CT’s can deliver up to 15 amps under these load conditions.
Example 8:
An electrician says a new three-phase 120/208 volt Wye service will require up
to 400 amps. Use the previously stated rule of thumb in reverse. Divide 400
amps by the Amps per kVA constant for a line to line voltage of 208 volts. 400
divided by 2.8 is approximately 143. 143 is the total kVA required. Each
transformer will need to be a minimum of 48 kVA to carry a balanced 400 amp
load. Install 3 – 50 kVA transformers which can provide up to 420 amps.
Current transformers with a 200/5 ratio with a RF of 2.0 would be appropriate.
A class 10 or 20 meter may be used.
Example 9:
An electrician says he needs to hook up a three-phase 40 HP 480 volt water
well. Most books list 1 HP = 746 watts, but when sizing equipment always assume
1 HP = 1 kVA. Therefore, 40 HP = 40 kVA. Three 15 kVA transformers are
required to provide a total of 45 kVA. Since the line to line voltage will be
480 volts, 40 kVA multiplied by 1.2 (480 volt Amps per kVA constant) = 48 amps.
Obviously a class 100 or 200 self-contained meter can be used for this load.
However, if you do not wish to use a 480 volt rated meter due to safety and
reliability concerns, use 480:120 volt voltage transformers with 50/5 ratio
CT’s. 200/5 CT’s with 1 turn may also be used if the water well has no
auxiliary light loads to worry about. If the water well is either on (full
load) or off (no load), then light load conditions which could cause accuracy
errors if CT’s are too large do not exist. (Always strive provide an instrument
rated meter with a minimum of .25 amps to improve light load accuracy).