Single Phase Amps
Purpose
Electrical services are usually sized by amperage, kilovolt-amps (kVA), or by
horsepower (HP) requirements. In order to size metering equipment properly, it
is often necessary to calculate amps when the transformer size (kVA) is known.
The
following formula may be used for calculating single-phase amps:
kVA X 1,000
Single-phase amps = -------------------------
Line to Line voltage
Example 1:
Assume you are using a 25 kVA 120/240 volt transformer. The line to line
voltage of the transformer is 240 volts. Therefore, use 240 volts in the
formula.
25 kVA X 1,000 25,000 VA
Single-phase amps = ------------------------- = ------------------- = 104
amps
240 V
240V
Rule of Thumb
Many
utilities greatly simplify the above formula with the following rule of thumb.
“If the line to line voltage of the transformer secondary is 240 volts, multiply
the kVA rating by 4”. Or, “If the line to line voltage of the transformer
secondary is 480 volts, multiply the kVA rating by 2”.
Example 2:
Assume you are using a 25 kVA 120/240 volt transformer with a line to line
voltage of 240 volts. Use the following formula.
Single-phase amps = 4 X 25 = 100 amps
Although the actual value was previously calculated to be 104 amps, this answer
is certainly close enough to size secondary conductors and metering equipment.
Example 3:
Assume you are using a 100 kVA 120/240 volt transformer with a line to line
voltage of 240 volts.
Single-phase amps = 4 X 100 = 400 amps
Example 4:
Assume you are using a 50 kVA 240/480 volt transformer with a line to line
voltage of 480 volts.
Single-phase amps = 2 X 50 = 100 amps
Never Add Amps!
Adding amps may be done under certain circumstances; however, it is also
responsible for many incorrectly sized electrical installations. Therefore,
unless you are certain you thoroughly understand how circuits work, it is best
not to get in the habit of adding amps.
Example 5:
In the following
diagram, amperage has been measured on both phases. Each phase has been
measured at 100 amps. This is a balanced 100 amp single phase load. Not a 200
amp load! The secondary conductors leaving the transformers and the rest of the
main service must be capable of carrying 100 amps not 200 amps. Do not
get in the habit of adding amps!
Metering Equipment & Transformer Sizing
Example 6:
An
electrician says a new single-phase 120/240 volt service will require up to 400
amps. Use the previously stated rule of thumb in reverse. Divide 400 amps by
4. The answer is 100. The service will require a 100 kVA transformer. Typical
self-contained meters can handle up to 200 amps. Since this service requires up
to 400 amps, an instrument rated meter with CT’s will be required. Although a
400:5 CT could be used, a better selection would be a 200:5 CT with a RF rating
of 2.0 or greater. The lower ratio CT improves the accuracy of the metering
when light load conditions exist.
Example 7:
An
electrician says he needs to hook up a single-phase 10 HP 240 volt water well.
Most books list 1 HP = 746 watts, but when sizing equipment always assume 1 HP =
1 kVA. Therefore, 10 HP = 10 kVA. A 10 kVA transformer is required. Since the
line to line voltage will be 240 volts, 4 X 10 = 40 amps. Obviously a class 100
or 200 self-contained meter can be used for this load.